YPP6200 Analog Input Flow Rate/Totalizer
Brand: Yokogawa Electric CorporationThe YPP6200 Meter is specifically designed for displaying flow rate and total from a flowmeter with an analog output, such as 4-20 mA or 0-10 V.
The YPP6200 is particularly well suited for flow applications because of its six-digit, dual-line display that can be programmed for a wide variety of display configurations.
Features- 0-20 mA, 4-20 mA, 0-5 V, 1-5 V, &plusm;10 V Inputs
- Rate Displayed as Units per Second, Minute, Hour, or Day
- Total, Grand Total or Non-Resettable Grand Total
- 9-Digit Totalizer with Total Overflow Feature
- Dual-Scale for Level Applications – Single Input
- Isolated 24 VDC @ 200 mA Transmitter Power Supply
- Signal Input Conditioning for Flow
- 32-Point Linearization, Square Root or Exponential Linearization
- Multi-Pump Alternation Control
- Large Dual-Line 6-Digit Display, 0.60" & 0.46"
- Sunlight Readable Display Models
- NEMA 4X, IP65 Front
- Programmable Display & Function Keys
- Universal 85-265 VAC, or 12/24 VDC Input Power Models
- 2 or 4 Relays + Isolated 4-20 mA Output Options
- External 4-Relay & Digital I/O Expansion Modules
- USB, RS-232, RS-485 Serial Communication Options
- Modbus® RTU Communication Protocol Standard
- Free PROPLUS Software for Operation, Monitoring, and Programming
Specifications
Accuracy
- ± 0.03 % of Calibrated Span ± 1 Count, Square Root
- ± 0.1 % of Full Scale at ± 0.004 mA - Isolated 4-20 mA Transmitter Output
- Programmable Exponent Accuracy Range: 10 to 100 % of Calibrated Span
Adjustment
- 2 Keys
- 4 Keys
Alarm
- High/Low
Approvals & Certifications
- CE
- UL
Communication
- Baud Rate: 300 to 19,200 bit/sec
- Data Length: 8-bits (1 Start Bit, 1 or 2 Stop Bits)
- Modbus RTU
- RS-232
- RS-422, RS-485
- Serial Communication Adapters
Current
- 1.5 mA Min. - Sink Current (Digital I/O Expansion Module)
- 10 mA - Max.
Deadband
- 0 to 100 % of Span, User Programmable - for Relays
Delay Time
- < 2 milliseconds (Fixed) - Turn Around Delay
- 0 to 999.9 seconds - Relays
Display
- 0 to 999,999 (up to 999,999,999 with Total-Overflow Feature)
- 6-Digit Large Dual-Line Display (-99,999 to 999,999)
- Red LEDs with Leading Zero Blanking
- Upper: 0.60” High, Lower: 0.46” High
Electrical Connectors
- 12 to 22 AWG
- Digital I/O
- Removable Screw Terminal
- RJ45 for External Relays
Electrical Rating
- 1/14 hp at 125/250 Vac for Inductive Loads - Relay
- 125/250 Vac Resistive Load - Relay
- 3 A at 30 Vdc - Relay
Enclosure, Body Material
- High Impact Plastic
Environmental Protection
- IP65
- NEMA 4X
Function
- Copy
- Gate - for Rate Display of Slow Pulse Rates
- Linear
- Password Protection
- Programmable Exponent from 1.0001 to 2.9999
- Round Horizontal Tank Volume Calculation
- Square Root
- Tare
Humidity
- 0 to 90 % Non-Condensing Relative Humidity
Input
- 0 to 1.25 Vdc - Low (Digital Input Logic)
- 0-20 mA
- -10-10 Vdc (0-5 V, 1-5 V, 0-10 V)
- 30 Vdc, Max.
- 3-5 Vdc - High (Digital Input Logic)
- 4-20 mA
- 5 A, Max.
- Modbus PV (Slave)
Input Impedance
- > 1 megaohms - for Voltage Ranges
- 50 to 100 ohms - for Current Ranges
Isolation
- 4 kV Input/Output-to-Power-Line
- 500 V Input to Output or Output to P+ Supply
Linearization
- 2 to 32-Points - Multi-Point Linearization
Loop Resistance
- 10 to 700 ohms - Output Loop Resistance for 24 Vdc Power Supply
- 100 to 1,200 ohms - Output Loop Resistance for 35 Vdc (External) Power Supply
Mounting
- 1/8” DIN Panel Cutout Required: 3.622” x 1.772” (92 x 45 mm)
- Panel Mounting Bracket
Operating Temperature
- -40° to 65° C (-40° to 150° F)
Output
- 0-0.4 Vdc - Low (Digital Output Logic)
- 2 or 4 Relays
- 23 mA - Max.
- 3.1-3.3 Vdc - High (Digital Output Logic)
- 4-20 mA
Output Noise
- > 60 dB at 50/60 Hz - Normal Rejection Mode
Power Options
- 12/24 Vdc ± 10 %, 15 W, Max.
- 85-265 Vac, 50/60 Hz
- 90-265 Vdc, 20 W, Max.
Power Requirement
- 12/24 Vdc Powered Models Rated at 100 mA - Max.
- 24 Vdc ± 5 % at 200 mA - Max.
- 24 Vdc ± 5 % at 40 mA - Max.
- 35 Vdc, Max.
- 5/10 Vdc at 50 mA - Max.
Programming
- Cloning Using Copy Function
- Digital Inputs
- Four Front Panel Buttons
- Modbus Registers
- PC & MeterView Pro Software
Rating
- 2 or 4 SPDT (Form C) - Internal (Relays)
- 4 SPST (Form A) - External (Relays)
Relay Operation
- Automatic (Non-Latching)
- Latching (Requires Manual Acknowledge)
- Off (Disable Unused Relays & Enable Interlock Feature, Manual ON/OFF Control Mode)
- Pump Alternation Control (2 to 8 Relays)
- Sampling (Based on Time)
- User Selectable Fail-safe
Span - Minimum
- 0.10 V - for Input ± 10 V
- 0.15 mA - for Input 4-20 mA
Storage Temperature
- -40° to 85° C (-40° to 185° F)
Switch Type
- Form C Relays
Thermal Drift
- 0.005 % of Calibrated Span/°C, Max.
- 0.01 % of Calibrated Span/°C, Max.
- 0.4 μA/°C, Max.
- 0.8 μA/°C, Max.
Torque
- 5 In/Lbs - Tightening Torque
Turn-Off Time
- 0.01 to 2.54 seconds - Byte-to-Byte Timeout
Update Time
- 200 milliseconds (5/second) - Display Update Rate