MXD Universal Computing Unit

Brand: Yokogawa Electric Corporation

This plug-in type universal computing unit receives DC current or DC voltage signals, applies various computing functions to them, and then converts them into isolated DC current or DC voltage signals.
Features
  • The optional Parameter Setting Tool (VJ77) or Handy Terminal (JHT200) can be used for the setting changes of various parameters such as computing functions or input/output ranges, the setting changes of programs, and the test outputs
  • The operation indicating lamp shows the operation status, abnormalities in a setting etc
  • Without a setting tool such as Handy Terminal etc., outputs can be adjusted and forced contact outputs can be turned on or off using the switches on the front panel.

Specifications

Accuracy

  • ± 0.1 % of Span

Consumption

  • 2.3 W at 24 Vdc - Power Consumption
  • 4.6 VA at 100 Vac - Power Consumption
  • 6.4 VA at 200 Vac - Power Consumption

Current

  • 40 mA DC or Less for Input Resistance of 250 ohms
  • 70 mA DC or Less for Input Resistance of 100 ohms

Duty Cycle

  • 100 ms - Computation Cycle

Electrical Connectors

  • M3.5 Screw Terminal

Electrical Rating

  • 0.1 mA at 5 Vdc - Contact Rating
  • 200 mA at 30 Vdc - Contact Capacity

Function

  • Analog Memory
  • Bottom Holder
  • Free Program
  • h
  • Peak Holder
  • Program Setter

Humidity

  • 5 to 90 % RH, Non-Condensing

Input

  • ± 15 Vdc or Less - Input Voltage

Input Signal

  • 0-10 mA DC, Span is 0.1 mA or more
  • 0-50 mA DC, Span is 1 mA or more
  • -10 to 10 Vdc, Span is 0.1 V or more
  • -2 to 2 Vdc, Span is 10 mV or more

Insulation Resistance

  • 100 MΩ or more at 500 Vdc between Input, Analog Output, Contact Output, Power Supply, & Grounding Terminals

Materials of Construction

  • Main Unit: ABS Resin + Polycarbonate Resin (Back), UL 94 V-0
  • Main Unit: PBT Resin, Including Glass Fiber (Black), UL 94 V-0
  • Socket: Modified Polyphenylene Oxide Resin, Including Glass Fiber (Black), UL 94 V-1

Mounting

  • DIN Rail Mounting
  • Wall Mounted

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Operating Voltages

  • 12-48 Vdc
  • 85-264 Vac

Output

  • 0-10 Vdc - Span is 0.1 V or more
  • 0-100 mVdc - Span is 10 mV or more
  • 0-20 mA DC - Span is 2 mA or more
  • 0-5 mA DC - Span is 1 mA or more
  • -10 to 10 Vdc - Span is 0.2 V or more
  • -100 to 100 mVdc - Span is 20 mV or more
  • Open Collector

Power Supply

  • 100-240 Vac (-15, 10 %), 50/60 Hz - Power Supply Rated & Input Voltage
  • 15-40 Vdc (± 20 %) - Power Supply Rated & Input Voltage

Power Supply Effect

  • ± 0.1 % of Span - Effect of Power Supply Voltage Fluctuations

Resistance

  • 1 MΩ (800 kΩ for 15-40 Vdc & 10 kΩ for 100-240 Vac During Power Off) - Input Resistance Voltage Signal
  • 100 ohms (External Receiving Resistor) - Input Resistance Current Signal
  • 250 ohms for the Optional Specification - Input Resistance Current Signal
  • 750 to 250,000 ohms - Permissible Load Resistance
  • OFF: 100 kΩ or more - Contact Input
  • ON: 200 ohms or Less - Contact Input

Response Time

  • 500 ms, 63 % Response (10 to 90 %)

Span & Zero Adjustments

  • ± 1 % of Span or More - Input Adjustment Range
  • ± 5 % of Span or More - Output Adjustment

Supply Voltage

  • 1,000 Vac for 1 Minute between Analog Output & Contact Output Terminals - Withstand Voltage
  • 2,000 Vac for 1 Minute between Input, (Analog Output & Contact Output), Power Supply & Grounding Terminals Mutually - Withstand Voltage

Temperature Effect

  • ± 0.15 % of Span or Less for a Temperature Change of 10° C (18° F) - Effect of Ambient Temperature
show more