EJX430B Wireless Pressure Transmitter
Brand: Yokogawa Electric CorporationThe High performance differential pressure and pressure transmitters EJX430B feature single crystal silicon resonant sensor and are suitable to measure liquid, gas, or steam flow as well as liquid level, density, and pressure.
These transmitters transmit not only process variables but also the setting parameters using wireless signal.
The transmitters run on internal batteries, and the installation cost can be decreased since hard-wiring is not required.
The communication is compliant with ISA100.11a protocol specifications.
FeaturesLong Life Battery Design
Ultra low current consumption design using two high capacity lithium-thionyl chloride batteries provide wireless operation for years.
Security Assured Wireless Network Joining
Infrared communication between the devices for wireless network configuration and parameter setting.
Quick Update Time
Selectable from 0.5 second to 60 minutes for measured process value to publish wirelessly.
Specifications
Accuracy
- ± (0.005 + 0.0035 URL/Span) % of Span - Capsule A & Capsule B
- ± (0.005 + 0.0049 URL/Span) % of Span - Capsule H
- ± 0.04 % of Span - Capsule H, Capsule A & Capsule B
Adjustment Type
- Zero Adjustment Screw
Ambient Temperature Range
- -30° to 80° C (-22° to 176° F) - LCD Visible Range
- -40° to 85° C (-40° to 185° F)
Approvals & Certifications
- Leak Test
- Material Certificate
- Pressure Test
- R & TTE Directive
Approvals & Certifications
- ATEX Intrinsically Safe
- CE ETSI EN 300328, ETSI EN 301489-1, ETSI EN 301489-17, EN 61010-1, EN 61010-2-030, EN 62311
- CSA Intrinsically Safe
- EMC EN 61326-1 Class A, EN 61326-2-3
- FCC Approval
- FM Intrinsically Safe
- IC
- IECEx Intrinsically Safe
- PED 97/23/EC, 2014/68/EU
Battery Life
- 10-Years - at 60 seconds Update Time
- 4-Years - at 10 seconds Update Time
BSP Connection
- 1/2” BSPT Female
- 1/4” BSPT Female
Burst Pressure
- psi: 10,000 (MPa: 69, bar: 690)
- psi: 6,800 (MPa: 47, bar: 470)
Communication
- Wireless Communication Protocol: ISA100.11a
Dead Time
- 100 milliseconds
Diagnostics
- Amplifier Failure
- Battery Alarm
- Capsule Failure
- Configuration Error
- Over-Range Error for Process Variables
- Wireless Communication Alarm
Diameter
- 0.44” (11.2 mm) - Sheath Diameter of Antenna Cable
Diaphragm Material
- Hastelloy C-276 - Capsule
Display
- 5-Digit Numerical Display
- 6-Digit Unit Display
- Bar Graph
- LCD Display
Drain, Vent Valves & Plug
- 316 Stainless Steel
- Hastelloy C-276
- Monel
Enclosure Finish
- Anti-Corrosion Coating
- Polyurethane Paint, Mint Green Paint (Munsell 5.6BG 3.3/2.9 or its Equivalent)
Environmental Protection
- IP66
- IP67
- NEMA 4X
Fill Material
- Fluorinated Oil - Fill Fluid
- Silicone - Fill Fluid
Flange Material
- ASTM CF-8M - Cover
- Hastelloy C-276 - Cover
- Monel - Cover
Fluid
- Gas
- Liquid
Frequency
- 2,400 to 2,483.5 MHz - License Free ISM Band
Gasket Material
- Fluorinated Rubber - Process Connector
- PTFE Teflon - Process Connector & Capsule
- Teflon-Coated 316L Stainless Steel - Capsule
Humidity
- 0 to 100 % Relative Humidity - Ambient Humidity Limits
Length
- 1.33” (34 mm) - Standard Long Vent Size
- 4.6” (119 mm) - Long Vent Size
Materials of Construction
- 304 Stainless Steel - Mounting Bracket
- 316 Stainless Steel - Mounting Bracket, Name Plate & Tag
Mounting
- 2” Pipe Mounting Bracket
Mounting Position
- Horizontal
- Universal
- Vertical
Mounting Position Effect
- Tilting up to 90° will cause Zero Shift up to 0.4 kPa
NACE & NIST
- NACE MR-0103
NPT Connection
- 1/2” NPT Female
- 1/4” NPT Female
Nut & Bolt Material
- 316L Stainless Steel
- 660 Stainless Steel
- B7 Carbon Steel
O-Ring Material
- Buna-N - Cover
Operating Temperature
- -20° to 80° C (-4° to 176° F)
Output
- Wireless (ISA100.11a Protocol) 2.4 GHz Signal
Overpressure & Static Pressure Limits
- psi: 2,300 (MPa: 16, bar: 160) - Max.
- psi: 3,600 (MPa: 25, bar: 250) - Max.
Power
- Maximum
Power Requirement
- 7.2 V, 19 Ah Lithium Thionyl Chloride Batteries
Pressure Range
- bar: -1 to 160
- Inches WC: -400 to 2,000
- MPa: -0.1 to 16
- psi: -14.5 to 2,300
Pressure Type
- Differential
- Gauge
Process Connection Material
- ASTM CF-8M
- Hastelloy C-276
- Monel
Process Temperature
- -40° to 120° C (-40° to 248° F)
Response Time
- 150 milliseconds
- 210 milliseconds - for H Capsule with Wetted Parts Material
Stability
- ± 0.1 % of URL Per 10-Years
Supply Pressure - Maximum
- Inches WC: 2,000 - Capsule H
- psi: 2,300 (MPa: 16, bar: 160) - Capsule B
- psi: 500 (MPa: 3.5, bar: 35) - Capsule A
- psi: 72.52 (kPa: 500, bar: 5) - Capsule H
Temperature Effect
- ± (0.04 % of Span + 0.009 % of URL) Per 28° C (50° F) - Capsule A & B Ambient Temperature Effect
- ± (0.04 % of Span + 0.0125 % of URL) Per 28° C (50° F) - Capsule H Ambient Temperature Effect
Update Time
- 0.5 to 3,600 seconds - Intermittent Measurement Mode
- 100 milliseconds - Continuous Measurement Mode
Vibration Effect
- < 0.1 % of URL - According to IEC 60770-1 Field or Pipeline with High Vibration Level (10-60 Hz, 0.21 mm Displacement / 60-2,000 Hz 3 G)
Wetted Materials
- 316L Stainless Steel
- F316L Stainless Steel
- Hastelloy C-276 - Capsule
- Monel - Capsule
- Tantalum - Capsule
Zero Offset
- External Zero is Continuously Adjustable with 0.01 % Incremental Resolution of Span
Documentation
Engineering Tools
- EJX110B, EJX310B, EJX430B Long Vent Plug (/U1) pdf 148 KB
- EJX310B, EJX430B Absolute and Gauge Pressure Transmitter with /N1 pdf 422 KB
- EJX310B, EJX430B Absolute and Gauge Pressure Transmitter with /N2 and /N3 pdf 426 KB
- EJX430B Gauge Pressure Transmitter Bottom Process Connection pdf 259 KB
- EJX430B Gauge Pressure Transmitter Universal Flange pdf 260 KB
- EJX430B Gauge Pressure Transmitter, Wetted Parts Material Code: H,M,T,A,D,B pdf 330 KB
- EJX430B Gauge Pressure Transmitter, Wetted Parts Material Code: S pdf 328 KB
Manual
- EJX B Series Device Description (DD) and Capabilities File (CF) zip 105 KB
- EJX B Series Device Description (DD) and Capabilities File (CF) for 3rd party GW zip 107 KB
- EJX-B Series Differential Pressure and Pressure Transmitters Manual Change pdf 196 KB
- EJX110B, EJX310B, EJX430B Differential Pressure and Pressure Transmitters pdf 5.0 MB
- Field Wireless Device Restart Tool (Instruction Manual) pdf 1.3 MB