SC210G Conductivity Detector

Brand: Yokogawa Electric Corporation

YOKOGAWA has been supplying superior on-line analyzers for monitoring or controlling the conductivity of liquid or solutions.

YOKOGAWA provides the four-wire conductivity converter, (SC450G), the two-wire conductivity transmitter (FLXA202/FLXA21, SC202).

YOKOGAWA also provides many kinds of detectors/ sensors for accurately measuring liquid conductivity when using converters/transmitters.

The combination of YOKOGAWA’s converters/ transmitter and detectors/sensors meets the demanding ultra pure water requirements of the growing semiconductor and pharmaceutical markets in addition to traditional water quality measurements for standard power plant and chemical applications.

Specifications

Approvals & Certifications

  • CSA
  • Material Certificate

BSP Connection

  • 1-1/2” BSPT Male
  • 1-1/4” BSPT
  • 1/2” BSPT Female

Cable Length

  • 9.84 to 65.61 feet (3 to 20 metres)

Electrical Connectors

  • M3 Ring Terminal
  • M4 Ring Terminal
  • Pin Terminal

Enclosure Finish

  • Epoxy Coated (Baked)

Enclosure, Body Material

  • 316 Stainless Steel
  • Polypropylene

Environmental Protection

  • JIS C0920 Watertight
  • NEMA 4

Flange Size - 1/2” (DN 15)

  • 1/2” (DN 15) - 150# (ANSI & JPI)
  • 1/2” (DN 15) - JIS 10K

Flange Size - 2” (DN 50)

  • 2” (DN 50) - 150# (ANSI & JPI)
  • 2” (DN 50) - JIS 10K

Flange Type

  • Flat Face (FF)
  • Raised Face (RF)

Flow Rate

  • < 20 L/minute - for Flow through Detectors

Materials of Construction

  • Polypropylene - Chamber Material
  • SCS14 - Chamber Material
  • Stainless Steel - Tag Plate

Measuring Range

  • 0-0.5 to 0-200 μS/cm (Cell Constant: 0.05 cm⁻¹)
  • 0 to 200 μS/cm to 0 to 20 ms/cm (Cell Constant: 5 cm⁻¹)

NPT Connection

  • 1/2” NPT Female
  • 1-1/2” NPT Male
  • 1-1/4” NPT Male

O-Ring Material

  • Fluororubber (FKM)
  • Perfluoroelastomer - FFKM

Pressure Range

  • psi: 0 to 145 (MPa: 0 to 1, bar: 0 to 10) - for Chamber Material: SCS14
  • psi: 0 to 72.52 (kPa: 0 to 500, bar: 0 to 5) - for Chamber Material: Polypropylene

Principle of Operation

  • 2-Electrode System

Seat / Seal Material

  • Perfluoroelastomer - Chamber Seal

Sensor, Probe Length

  • 5.90” to 78.74” (150 to 2,000 mm) - Sensor Length

Sensor, Probe Material

  • 316 Stainless Steel
  • Glass
  • Platinum

Sensor, Probe Type

  • Thermistor (PB36NTC)

Temperature Range

  • 0° to 100° C (32° to 212° F) - for Chamber Material Polypropylene
  • 0° to 105° C (32° to 221° F) - for Chamber Material SCS14
show more